This propane infrared straight tube heater is designed for commercial buyers heating complete buildings. It delivers infrared heat through a 40-foot tube system to support comfortable, even energy distribution in larger indoor spaces.
The heater provides 175,000 BTU output and uses a positive-pressure combustion chamber with direct spark ignition and 100% gas shut-off safety control. Gas and electrical connections are located at the same end. It requires a 120V supply and can operate with an external 24V thermostat or line voltage. The unit measures 122 in. long by 18 in. wide by 16 in. high and includes aluminum reflectors, a cast-iron burner, diaphragm air switch, burner inspection sight glass, diagnostic monitoring lights, and an internally located blower with a permanently lubricated ball-bearing motor. It supports up to 40 ft. of fresh-air ducting or 40 ft. sidewall venting.
Key Features:
- 40-Foot Straight Tube: Provides extended infrared heat coverage for complete-building heating layouts.
- 175,000 BTU Output: Supplies substantial heating capacity for commercial building applications.
- Same-End Connections: Places gas and electrical hookups together to simplify installation planning.
- Direct Spark Ignition: Provides dependable ignition during operation.
- Internal Blower: Keeps the blower inside the burner box for applications where low noise is preferred.
- Thermostat Compatibility: Allows control through an external 24V thermostat or line-voltage operation.
Choose this propane infrared heater when a 40-foot straight-tube configuration, high-output building heat, and same-end utility connections suit the planned installation.
| Country of Origin: |
US |
| Material: |
Cast Iron/Aluminum |
| Product Depth: |
18 |
| Product Height: |
16 |
| Product Type: |
Gas Infrared Heaters |
| Product Width: |
122 |
| Quantity Included: |
1 |
| Voltage: |
120 V |
| Length: |
42 in |
| Weight: |
161.6 lbs |
| Burner Pressure: |
10 in |
| Clearance to Combustibles Bottom: |
86 in |
| Duct Size: |
4 in |
| Gas Inlet Pressure Max Water Column: |
14 in |
| Min Mounting Height: |
15/16 ft |
| Tube Length: |
40 ft |
| Amperage: |
1.8 A |
| BTU: |
175000 BTU |
| Fuel Type: |
Propane |
| Ignition Type: |
Direct Spark |
| Includes: |
Diaphragm Air Switch, Cast Iron Burner, Burner Inspection Sight Glass |
| Mounting Location: |
Wall or Ceiling |
| Phase: |
1 |
| Power Cord Type: |
Plug-in |
| Shape: |
Straight |
| Tube Material: |
Steel |
| Type: |
Positive Pressure Tube |
| Warranty: |
1 yr |
| Certifications: |
CSA |
| Shipping Method: |
LTL |
| Width: |
18.00
in
|
| Height: |
16.00
in
|
| Depth: |
122.00
in
|
No additional information available.