Commercial and industrial facility operators can use this gas-fired infrared straight tube heater to provide radiant heat in large work and storage areas. Its 40-foot straight configuration is suited to facilities that need a packaged tube-heating system.
This pre-engineered, power-vented system has a 175,000 BTU rating and a 40-foot straight tube configuration with a 4-inch OD emitter tube. The package includes a powder-coated aluminized steel burner, heat-treated aluminized steel radiant tubes, bright-finish aluminum reflectors, tube and reflector hangers, intermediate supports, joint sealer, screws, a turbulator, a stainless steel flexible gas connector with manual gas valve, and two reflector end caps. Overall dimensions are 13.5 inches wide, 492.75 inches deep, and 10.5 inches high.
Key Features:
- 175,000 BTU Rating: Provides substantial heating capacity for commercial and industrial spaces.
- 40-Foot Straight Configuration: Offers a long, straight tube layout for planned overhead heater installations.
- Power-Vented Design: Uses a positive-pressure, push-through system configuration.
- Complete System Package: Includes key burner, tube, reflector, support, and connection components.
- Aluminum Reflectors: Bright-finish reflectors are included as part of the heater system.
Choose this straight tube infrared heater for commercial or industrial facilities requiring a 175,000 BTU, 40-foot power-vented system. Installation must be completed by an HVAC contractor qualified to install and service gas-fired heating equipment in accordance with applicable local codes and regulations.
| Color/Finish: |
White |
| Country of Origin: |
US |
| Material: |
Aluminized Steel/Aluminum |
| Product Depth: |
13.5 |
| Product Height: |
10.5 |
| Product Type: |
Gas Infrared Heaters |
| Product Width: |
492.75 |
| Quantity Included: |
1 |
| Warranty: |
3 Year Burner/10 Year Tube |
| Color: |
White |
| Length: |
41-1/16 in |
| Weight: |
131 lbs |
| Burner Pressure: |
10 in |
| Clearance to Combustibles Bottom: |
72 in |
| Clearance to Combustibles Side: |
42 in |
| Clearance to Combustibles Top: |
7 in |
| Duct Size: |
4 in |
| Gas Inlet Pressure Max Water Column: |
14 in |
| Max Mounting Height: |
30 ft |
| Min Mounting Height: |
16 ft |
| Tube Length: |
40 ft |
| Amperage: |
1.4 A |
| BTU: |
175000 BTU |
| Fuel Type: |
Propane |
| Ignition Type: |
Direct Spark |
| Includes: |
NPT Stainless Steel Gas Flex |
| Mounting Location: |
Ceiling |
| Phase: |
1 |
| Power Cord Type: |
Hard Wired |
| Shape: |
Straight |
| Tube Material: |
Aluminized Steel |
| Type: |
Positive Pressure Tube |
| Voltage: |
110 V |
| Wattage: |
51287 W |
| Watts High: |
51287 W |
| Certifications: |
CSA |
| Shipping Method: |
LTL |
| Width: |
13.50
in
|
| Height: |
10.50
in
|
| Depth: |
492.75
in
|
No additional information available.